Water heaters ARTO DB

Water heaters ARTO DB

Horizonal / Vertical double wall water heater

ARTEMIS double wall water heaters are suitable for use in Commercial and Industrial applications for the production of Domestic Hot Water (DHW).

The ARTO DB series come in capacity range from 500 to7000 lt

  • Capacity :  500/1000/1500/2000/2500/3000/4000/5000/6000/7000 lt
  • Max. Working Pressure of Internal Cylinder : 10 bar
  • Max. Working Pressure of External Cylinder : 4 bar
  • Max. Working Temperature : 95 0C
  • Domestic Hot Water (DHW) 

Larger sizes and higher pressure upon request

Ideal for installations with central heating systems

ARTEMIS Industry focuses on the particularity of each client’s needs. Therefore, the Company has a great flexibility to produce products that differ a lot from those of the mass production. Many features such as :

  • heating surface
  • thickness of metal sheets
  • working pressure
  • insulation e.tc

can be adjusted to the special needs of each customer, especially Industries and big PublicBuildings.

  • Pressures up to 10 bar ensure that the boiler is suitable for big installations
  • The internal tank (DHW) acts also as a large thermal store
  • The internal tank is surrounded by primary hot water to almost all its length
  • Large heat transfer surface enables a high volume of DHW to be heated in a short time
  • Cathode protection through Magnesium Anode is only available upon request.
  • Can be supplied either horizontal or vertical , depending on the special specifications of the place of installation

 

Insulation :

 Low heat losses through high density mineral wool protected by :

  • Aluminium cover sheets
  • Hot galvanized cover sheets, coloured in blue
  • Stainless steel cover sheets

 

Depending on the customer’s needs and the particularities of each installation can be either insulated or not.

  • When filling the heater with water beware that you first fill the internal cylinder (DHW) and then the external (Primary Heating Water)
  • Fit a safety valve below the inner tanks maximum working pressure
  • Fit a non-return valve to DHW cold inlet
  • Don’t forget to install an expansion vessel to the primary heating circuit (return)
  • Don’t forget to connect the inner tank to the earth.
  • Hot water should not be stored at temperatures below 60 0C, to avoid the risk of Legionella.

 

ARTEMIS has made a simple electronic panel that provides protection against Legionella. The temperature of the sanitary water rises periodically

at 75 0C for 10 minutes. Then the system returns to the initial situation

Hotels

Hospitals – Public buildings

Swimming Pools- Gyms

Industry